Information on Thermoelectric Tripping Devices (Electronic Fusible Links)
- How it works: These devices combine an electrical switch with internal temperature sensors. They are placed inside or right outside air ventilation ducts.
- The Trip Mechanism: If the duct or ambient air temperature exceeds a pre-determined threshold (typically 72°C / 165°F), the device opens its electrical contacts. This immediately cuts power to a spring-return actuator, causing it to snap close.
- Industry Example: The Belimo BAT Thermoelectric Tripping Device is universally used across HVAC fire and smoke dampers.
|
Technical Data |
BAT72 |
|---|---|
|
Nominal voltage |
AC/DC 24 V |
|
Nominal voltage frequency |
50/60 Hz |
|
Rated Current |
1 A |
|
AC/DC throughput resistance |
<1 Ω |
|
Connection supply |
Cable 1 m, 2x 0.75 mm², Betaflam cable heatresistant up to 145°C |
|
Probe length |
65 mm |
| Response temperature thermal fuse |
Duct inside temperature 72°C (colour black) Duct outside temperature 72°C |
|
Protection class IEC/EN |
III, Safety Extra-Low Voltage (SELV) |
|
Degree of protection IEC/EN |
IP54 |
|
EMC |
CE according to 2014/30/EU |
|
Low voltage directive |
CE according to 2014/35/EU |
|
Hygiene test |
According to VDI 6022 Part 1 |
|
Rated impulse voltage supply |
0.8 kV |
|
Pollution degree |
3 |
|
Ambient humidity |
Max. 95% RH, non-condensing |
|
Ambient temperature |
-30...55°C [-22...131°F] |
|